The Sunny Island 3324/4248 is the system manager of a stand-alone power sup¬ply. Its service life of over 20 years makes it a future-proof investment. The Sunny Island 3324/4248 also works reliably under extreme ambient conditions, such as high temperatures or excessive dust. The AC coupling developed by SMA provides maximum flexibility in expanding the system and reduces installation efforts and costs. Other AC sources can be easily connected to the AC bus and therefore substan¬tially increase performance an the AC side. This allows batteries and generators to be dimensioned smaller. The integrated smooth startup mode allows all loads to be started safely.

  • Suitable for systems from 2 kW to 5.4 kW
  • The only inverter with AC coupling for all energy sources
  • Fully automatic uninterrupted Operation
  • Robust and reliable
  • Excellent overload characteristics
  • Easy installation
  • Long battery service life thanks to Optimum battery management system
  • Compatible with Sunny Family products

Technical data

 

Technical data
  SI 3324 SI 4248
Input data
Input voltage 230 V (172,5 – 250 V) 230 V (172,5 – 250 V)
Input frequency 50 Hz (40 – 60 Hz) 50 Hz (40 – 60 Hz)
Max. AC input current 56 A (2 – 56 A) 56 A (2 – 56 A)
Max. input power 12,8 kW 12,8 kW
Output data
Rated AC voltage (adjustable) 230 V (202 – 253 V) 230 V (202 – 253 V)
Grid frequency (adjustable) 50 Hz (45 – 55 Hz) 50 Hz (45 – 55 Hz)
Continuous AC output at 25 °C / 45 °C 3300/2300 W 4200/3400 W
Continuous AC output at 25 °C for 30 / 5 / 1 min 4200/4400/5000 W 5400/6200/7000 W
Rated AC current 14,5 A 18 A
Max. current (peak value) for 100 ms 70 A 100 A
Output voltage harmonic distortion factor < 3 % < 3 %
Power factor –1 bis +1 –1 bis +1
Battery data
Battery voltage (range) 24 V (21 – 32 V) 48 V (41 – 63 V)
Max. battery charging current 140 A 100 A
Continuous charging current 104 A 80 A
Battery capacity 100 – 6000 Ah 100 – 6000 Ah
Charge control lUoU with automatic full charge and equalization charge
Efficiency/power consumption
Max. efficiency (typical) 94,5 % 95 %
Own consumption (no load/standby) 22 W (< 4 W) 22 W (< 4 W)
Protection type acc. to DIN EN 60529 IP30 IP30
Device protection Short-circuit, overload, overtemperature
Interfaces
  2 LEDs, 4 buttons, 2-line display, 1 relay for
load break, 1 relay for diesel generator con
trolling, RS485/RS232 electrically separated
(optional)
Mechanical data
Width / Height / Depth in mm 390 / 590 / 245 390 / 590 / 245
Weight 39 kg 39 kg
Ambient conditions
Ambient temperature from -25 °C to +50 °C from -25 °C to +50 °C
Guarantee (EU) 2 years 2 years
Accessories
Ext. Battery temperature sensor included included
Generator management "GenMan optional optional